CSI Ningdong N160 Series Diesel Generator Set (200 – 400kW)

Product Description

The generator set, comprising a generator and CSI Ningdong N160 series diesel engine mounted on a common baseframe, fully completed with essential auxiliaries, is an ideal standby emergency power supply for small-sized industrial and mining enterprises, hotels, rural areas, etc. The generator combined with all auxiliaries can be accommodated in a 20’ sound-proof container that is an efficient answer for isolated developing regions which do not have alternative energy sources and for those applications where mobility and fast installation of energy plants are required.

Model Portfolio Table

Generator Model 200GF 250GF 280GF 300GF 350GF 400GF
Rated output (kW) 200 250 280 300 350 400
Engine Model N6160ZLCD2 N6160ZLCD6 N6160ZLCD8 N8160ZLCD6 N8160ZLCD N8160ZLCD16
Bore x Stroke (mm) 160 x 200
Engine Type Four-Stroke, In-line, direct Injection, Turbocharged, Intercooled
Engine Rated Power (kW) 235 294 331 353 400 464
Speed (rpm) 50Hz@1000 / 60Hz@1200
SFOC (g/kW·h) 196+3%

Electrical Performance

 

Voltage

Voltage no-load regulation range % 95~105
Voltage fluctuation rate % ±1
Steady state voltage regulating rate % ±2.5
Transient voltage regulating rate % ±20~-15
Stabilization time s 1
Alternator Excitation method   Brushless AVR
 

Frequency

Steady-state frequency (rev.) regulating rate % 5
Frequency (rev.)  fluctuation rate % ±0.5
Transient frequency regulating rate % ±10
Stabilization time s < 5
Frequency regulating method  

 

Auto / Manual
 

Protection

Over Speed 115% Nr   A, T, S Reverse Power -9.6% Pn A, T
LO. Pressure 0.25MPa A, 0.15MPa T, S Over Current 130% In A, T
Freshwater Temperature 80℃ A, 85℃ T, S Over Voltage 120% Vn A, T
LO. Temperature 90℃ A Overload 110% In A

Notes: All engine rating data is based on ISO 3046/1.
Reference conditions: Ambient 45℃, Relative humidity 60%, Intercooler coolant inlet 32 ℃.
If test ambient conditions are not the same as the fiducially ambient conditions. The power shall be revised according to ISO3046-1: 2002.
Fuel characteristics: MDO, Lower heat value:42700kj/kg, Consumption tolerance: +5%.
Power: An overload of 10% is permitted for one hour every twelve hours of operation.

Characteristics:

  • Meet with: ISO8528, ISO3046, GB/T13032.
  • Marine medium speed engine driven, unrestrictedservice configured, IMO Tier II D2 certified.
  • Brushless self-excited alternator with AVR, G3 electricity quality.
  • Application:Power plant set, Emergency automatic start power, Marine Auxiliary power, Container type diesel generator set.
  • As offer customized power plant solutions with multi-options fuels of diesel, LPFO/HFO, biofuel, natural gas, tire pyrolysis oil, etc.
  • Easy installation, high reliability, low noise, low operating cost, and environmentally friendly.

Outline

CSI Ningdong DF170 Series Dual Fuel Generator Set (200 - 500kW) 01

Gensets Dimensions(approx.)

Model A B C D Weight
mm mm mm mm (kg)
200GF 3755 1328 1807 399 5500
250GF 3755 1328 1807 399 5600
280GF 3852 1435 1807 442 5800
300GF 4472 1377 1975 474 6800
350GF 4472 1377 1975 474 6800
400GF 4546 1250 1975 637 7400

Remarks: Dimensions and weight are for reference only. For generator set model selection, please make communicate with relevant personnel. The delivery scope for each model engine shall be performed as per the corresponding technical files.